Navien Furnace: Installing the vent drain option
Installing the vent drain option on a Navien furnace: Use when vent runs through an unconditioned space like an attic or crawl space to stop condensate building up in the inducer housing.
Applies to: NDF600 series furnaces with vent through unconditioned space
Common causes of installing the vent drain option
- Vent passes through an unconditioned space
- Condensate collects in the inducer housing during cycling
How to fix installing the vent drain option: step by step
- Place a tee of the correct size (2 in or 3 in) in the horizontal run or vertical riser closest to the furnace.
- Fit a 5/8 in (15.9 mm) reducer bushing into the tee stem.
- Fit a piece of 5/8 in (15.9 mm) pipe at least 3 in (76 mm) long into the reducer as a nipple.
- Connect flexible drain tubing such as EPDM rubber or PVC to the nipple.
- Loop the drain tubing to form a trap.
- Connect the discharge end of the drain tube to the external condensate disposal system.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF Forced Air Gas Furnace Installation and Operation Manual, p. 20. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.