Navien Furnace: Installing the pressure relief valve
Installing the pressure relief valve on a Navien furnace: Install a 30 psi maximum pressure relief valve on the 3/4 in adapter on the upper cover. The valve must be ASME certified and installed only by a licensed professional.
Applies to: NPF700 all models
How to fix installing the pressure relief valve: step by step
- Apply thread seal tape to the threads of the valve before installing.
- Install the valve at the furnace outlet in the vertical position.
- Point the drain outlet horizontally out the side of the valve, then elbow down.
- Do not install any valve between the relief valve and the furnace.
- Run an outlet line toward the drain pan and make sure it drains properly.
- Do not reduce the discharge line or fit anything that restricts flow.
- Do not plug the relief valve.
- Keep the discharge from splashing hot water on an operator or the furnace.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 32. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.