Navien Furnace: Installation checklist: location, clearances and gas supply
Installation checklist: location, clearances and gas supply on a Navien furnace: Confirm before commissioning that the location and gas supply are correct. Each item must be a yes before the install is complete.
Applies to: NPF700 series (all listed models)
How to fix installation checklist: location, clearances and gas supply: step by step
- Confirm required clearances from building openings and intake vents, and keep the vent termination as close to the furnace as practical.
- Confirm service clearances, make-up air and that the area is free of dust, corrosive elements and flammable vapors.
- Confirm the furnace and vent piping are clear of combustibles such as clothing, cleaning materials and rags.
- Install the pressure relief valve. If auto water fill is not used, fill the water tank manually. If auto fill is used, confirm the water line is installed.
- Confirm the gas supply type matches the rating plate.
- Confirm the gas line is at least 1/2 in or 3/4 in ID and is long and large enough to deliver the required BTU load.
- Measure the gas supply line pressure and confirm it is inside the range in the manual.
- Confirm a manual gas shut-off valve is installed.
- Pressure-test the gas line and all fittings for leaks.
- Confirm the gas company has inspected the installation if required.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 92. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.