Navien Furnace: Gas line purging and pressure test precautions
Gas line purging and pressure test precautions on a Navien furnace: Never use an open flame to check gas line leaks. Disconnect the manual shut-off valve and the gas valve for any pressure test above 1/2 psig (3.45 kPa). Avoid high pressure at the gas valve and use a backup wrench to prevent twisting it.
Applies to: NDF gas piping
How to fix gas line purging and pressure test precautions: step by step
- Do not use a match, lighter, flame or other ignition source to find leaks.
- Disconnect the manual shut-off valve and gas valve before pressure testing above 1/2 psig (3.45 kPa).
- Keep the gas valve clear of high pressure.
- Hold the gas valve with a backup wrench when tightening fittings.
- Install the manual gas shut-off valve and dirt pocket as close to the furnace as possible, readily accessible, and at the height local code requires (4 to 5 ft / 1.2 to 1.5 m above floor level where required).
If the unit shows an error code, look it up: Navien Furnace codes
More commissioning tips for furnace
Source: Navien NDF Installation and Operation Manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.