Navien Furnace: Draining the water tank and condensate trap (upflow and downflow models)
Draining the water tank and condensate trap (upflow and downflow models) on a Navien furnace: Use this to empty the water side when the furnace will sit unused for a long time. Damage from freezing is not covered by the warranty.
Applies to: NPF700 upflow and downflow models
How to fix draining the water tank and condensate trap (upflow and downflow models): step by step
- Turn each knob on the upper front cover counterclockwise, remove the cover, then pull the lower front cover back and out.
- Connect the 3/4 in condensate hose from the installation kit to the drain adapter.
- Turn the drain valve on the drain adapter 90 degrees clockwise, then lift the lever on the pressure relief valve to open it.
- Drain the water tank for more than 5 minutes, then close the drain valve and the pressure relief valve.
- Remove the four screws from the bracket holding the front control panel and sub controller, then take them out of the furnace.
- Connect a 1/4 in pipe to the circulation pump drain adapter. On downflow models, also connect a pipe to the water coil drain adapter. Turn the drain cock on the adapter counterclockwise to open it.
- After the circulation pump is fully drained, close the drain cock. On downflow models only, the water coil drain valve is also present.
- Remove the end cap and stopper from the condensate trap and drain the water, then reinstall the cap and stopper.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 142-143. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.