Navien Furnace: Connecting the condensate drain
Connecting the condensate drain on a Navien furnace: Furnace condensate is acidic (pH about 3 to 5). Dispose of it according to local codes. Choose one of three disposal options and follow the drain rules.
Applies to: All NPF700 models
Common causes of connecting the condensate drain
- Condensate line blocked or frozen, which can cause condensate to back up and damage the furnace
- Drain line without enough slope
- Trap not primed
How to fix connecting the condensate drain: step by step
- Choose one disposal option: (a) direct from the furnace into an external drain; (b) through a neutralizing agent and then into an external drain; or (c) into a condensate pump and then into a suitable drain. Use a pump when the accessible drain is far away.
- If using a neutralizer, replace the neutralizing agent periodically, following the neutralizer manufacturer's guidance. Depletion depends on how much the furnace runs.
- Use only the drain trap supplied with the furnace, and prime it during installation.
- Give the drain line a downward slope of 1/4 in. per foot toward the drain.
- Do not add any trap onto the drain line coming from the furnace.
- Protect the line from freezing wherever it may see near or below freezing temperatures.
- Do not cap or plug the condensate line, and do not let it become obstructed.
- If an air conditioning coil shares the drain, install an open tee in the drain line near the cooling coil to relieve positive pressure from the coil plenum so the furnace trap keeps working.
- Connect to the furnace drain at the NPT 3/4 in. connection.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 39-40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.