Navien Furnace: Connecting an A/C evaporator drain to the furnace drain
Connecting an A/C evaporator drain to the furnace drain on a Navien furnace: If an air conditioner evaporator coil shares the furnace drain line, its drain must join downstream of the trap, not upstream.
Applies to: NDF with air conditioner evaporator drain
How to fix connecting an a/c evaporator drain to the furnace drain: step by step
- Install a tee fitting (field supplied) on the trap outlet.
- Connect the evaporator coil condensate drain to the tee, downstream of the trap.
- Do not connect the evaporator drain upstream of the furnace trap.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF Installation and Operation Manual, p. 45. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.