Navien Furnace: Checking venting after removing an old furnace

Updated · by Aurora Star Tech Inc.

Checking venting after removing an old furnace on a Navien furnace: When an existing furnace is taken out of a shared venting system, the remaining appliances may no longer vent properly. Test the remaining appliances with this procedure, which follows ANSI Z21.47 / CSA 2.3 section 4.23.6.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Removing an existing furnace from a shared vent system

Common causes of checking venting after removing an old furnace

  • Vent system is too large for the remaining attached appliances
  • Blockage, restriction, leakage, corrosion or other defect in the vent system

How to fix checking venting after removing an old furnace: step by step

  1. Inspect the venting system for correct size and horizontal pitch, and check for blockage, restriction, leakage, corrosion and other defects. Confirm the system meets the requirements of the new NPF unit, or replace it with a properly sized system.
  2. Close all building doors and windows, and the doors between the appliance space and the rest of the building, as far as practical.
  3. Close fireplace dampers.
  4. Turn on clothes dryers and any appliance not connected to the vent. Turn on range hoods and bathroom exhaust fans at maximum speed. Do not run a summer exhaust fan.
  5. Start the appliance being checked and set the thermostat so it runs continuously.
  6. After 5 minutes of main burner operation, check the draft hood relief opening of the other appliances for spillage using a match or candle flame.
  7. If venting is improper, correct the venting system according to the National Fuel Gas Code ANSI Z223.1/NFPA 54 or CSA B149.1-15. Resize per the appropriate table in Appendix G of the code.
  8. When every appliance passes, return doors, windows, exhaust fans, fireplace dampers and other gas appliances to their original condition.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Furnace codes

Source: Navien NPF installation and operation manual, p. 33. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.