Navien Furnace: Check supply duct static at the coil test hole
Check supply duct static at the coil test hole on a Navien furnace: Supply static is read between the furnace and cooling coil; return static is read between the filter and blower.
Applies to: NPF700 hydro-furnace with evaporator coil
Common causes of check supply duct static at the coil test hole
- Excessive external static causes low airflow, high temperature rise, limit trips and short equipment life.
How to fix check supply duct static at the coil test hole: step by step
- Remove the A-shaped block-off plate on the coil end.
- Drill a test hole in the plate and reinstall the plate.
- Take the supply static reading at the test hole.
- Take the return static reading between the filter and the furnace blower.
- Tape the test hole closed after the test.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NPF installation and operation manual, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.