Navien Furnace: Check horizontal vent slope and support
Check horizontal vent slope and support on a Navien furnace: Confirm horizontal vent runs drain condensate back toward the furnace and are supported correctly.
Applies to: NDF600 series furnaces
How to fix check horizontal vent slope and support: step by step
- Slope horizontal piping back toward the furnace at a minimum of 1/4 in per foot (18 mm per meter).
- Support horizontal runs at least every 5 ft (1.524 m).
- Confirm there are no dips or sags in horizontal sections.
- Make sure the exhaust is supported before it is fitted to the inducer; the inducer must carry no weight of the vent system.
- Insulate vent runs in unconditioned space where freezing may occur, unless heat tape is applied.
- Where water may collect in horizontal runs, wrap with self regulating 3 or 5 watt heat tape that is CSA, UL or ULC listed and installed per its instructions.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.