Navien Furnace: Check furnace input rate
Check furnace input rate on a Navien furnace: Calculate input from the gas heating value and the time for the meter dial to move 1 cu ft. Adjustments to burner manifold pressure must be made with a manometer or calibrated Magnehelic gauge.
Applies to: Furnace input verification
Common causes of check furnace input rate
- Gas heating value differs from the 1,000 Btu/ft³ basis, for example 900 gives about 90% input and 1,100 gives about 110%
How to fix check furnace input rate: step by step
- Calculate input in Btu/hr: heating value of gas (Btu/ft³) × 3600 divided by the seconds needed for 1 cu ft.
- If using SI meter units: 1 cu ft = 0.0283 m³, 0.01 m³ = 0.3531 cu ft, 0.5 m³ = 1.766 cu ft.
- Compare the result with the rating plate input.
- Never adjust input above the rating plate input.
- If correction is needed, adjust manifold pressure only within ±0.3 in. w.c. of the rating label value, or change the orifice size.
- Confirm the gas supplier's heating value before adjusting.
If the unit shows an error code, look it up: Navien Furnace codes
Source: Navien NDF installation and operation manual, p. 52. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.