Common causes of ch series noise problems

  • Unit not level or loose on the wall
  • Fan out of balance
  • 3-way valve micro switch keeps the motor running
  • Gas-air differential set wrong
  • Main gas valve proportional valve faulty
  • Air pressure sensor faulty or APS hose torn
  • Exhaust being pulled into intake
  • Low gas pressure (flame lifting)
  • Dirty nozzles
  • Heat exchanger scaling (boiling noise)

How to fix ch series noise problems: step by step

  1. Vibration: check the mounting and level. Touch the fan. If it shakes or the noise stops with the case lid off, replace the fan motor.
  2. Constant motor noise: 3-way valve micro switch fault. Replace the 3-way valve.
  3. Pop or bang at ignition: check the gas-air differential at 3-stage min (DIP 1 and 2 ON). 210/240 standard is 17±1 mm H2O. If noise stays at standard, adjust a little above or below.
  4. Whistle or rumble while firing: check inlet gas pressure, nozzles, APS and APS hose (noise can come and go with hose damage).
  5. Compare the flame on stages 1, 2 and 3. An uneven section points to a dirty nozzle.
  6. Check spacing between intake and exhaust and between units.
  7. Boiling noise check: raise water to 158°F (70°C) and listen.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.1 Noise p.108. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.