Updated · by Aurora Star Tech Inc.

CH series no space heat while burner runs / warm floor with heat off on a Navien combi boiler: Symptom guide for CH boilers that fire but do not heat the zones, short cycle on low flow, or put heat into the floor when heating is off.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series no space heat while burner runs / warm floor with heat off

  • Heating strainer plugged
  • Distributor or old piping plugged, or only one zone valve open
  • Pump impeller worn or slow
  • Supply or return thermistor reading high
  • Small DHW leak or pressure changes trigger the 5-minute DHW wait
  • 3-way valve not switching or leaking past (heat into floor)

How to fix ch series no space heat while burner runs / warm floor with heat off: step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Clean the heating strainer and find the source of debris.
  3. Open the distributor valves and balance them. One open zone alone slows heating.
  4. Check pump output. Replace if the impeller is worn.
  5. Compare sensor readings with real temps. Replace a thermistor that reads high.
  6. Unplug the flow sensor and run heat. If it now heats, a small DHW leak or a booster pump on the cold line is making the unit wait in DHW mode.
  7. Warm floor with heating off: the 3-way valve is not closing the heating side. Replace the 3-way valve.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 p.110. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.