Navien Combi Boiler: CH series hot water problems (cold, lukewarm or none)

Updated · by Aurora Star Tech Inc.

CH series hot water problems (cold, lukewarm or none) on a Navien combi boiler: Symptom guide for CH combis with no hot water, low hot water temperature or cold slugs.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series hot water problems (cold, lukewarm or none)

  • Hot and cold pipes swapped
  • Flow sensor sticking
  • 3-way valve not switching to DHW
  • Supply thermistor reading high
  • DHW heat exchanger leaking cold into hot
  • Setpoint set low
  • Water pressure/flow too high for the unit
  • Cold water mixing at the fixture or crossover
  • Plugged cold water filter or frozen pipe
  • Debris in internal circulation

How to fix ch series hot water problems (cold, lukewarm or none): step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check hot and cold connections are not swapped.
  3. Check the hot water setpoint on the remote.
  4. Flow sensor: cleaning can work for now, but replace it. Flow should read 00 with no draw.
  5. 3-way valve: if DHW temp does not rise while firing, check the heating outlet pipe. Check 120 VAC Blue+Black at the valve. No power = PCB.
  6. If the remote shows hot water but the tap is cold, suspect the supply thermistor reading high. Replace it.
  7. Burner runs fine but DHW stays low: DHW heat exchanger may be mixing cold in. Replace it.
  8. Too much flow for the unit: fit a pressure reducing valve. Example in manual: CH-210 gives 4.5 GPM at a 77°F rise.
  9. Hot at the unit but cold at the tap: look for crossover or a faulty mixing tap.
  10. Check the cold water valve is open, the cold water filter is clean and pipes are not frozen.
  11. Touch both sides of the DHW heat exchanger. A big difference means it is plugged.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 Hot water p.109. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.