Navien Combi Boiler: CH series E021 / E022 cold water inlet thermistor – full check
CH series E021 / E022 cold water inlet thermistor - full check on a Navien combi boiler: E021 = cold inlet sensor open (14°F or less). E022 = cold inlet sensor shorted (248°F or more). The boiler goes to safety shutdown after 3 seconds.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e021 / e022 cold water inlet thermistor - full check
- Loose or wet connector
- Failed thermistor
- Bad PCB
How to fix ch series e021 / e022 cold water inlet thermistor - full check: step by step
- Turn off power before unplugging connectors or measuring resistance.
- Check the plug and harness for looseness or water.
- Unplug from the PCB and measure the blue pair at CN13: 0.8-20 kOhm is normal.
- Open or 0 ohm = replace the sensor.
- If the sensor is good, replace the PCB.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.19 21 Error p.94-95; 5.20 22 Error p.96-97. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.