Navien Combi Boiler: CH series E013 pump – full check
CH series E013 pump - full check on a Navien combi boiler: After the pump starts, the board expects system pressure to change within 7 seconds. It tries 3 times. No change = E013, manual reset.
Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers
Common causes of ch series e013 pump - full check
- Pump stuck (debris in heating water)
- No power to pump, bad start capacitor or open coil
- Air in the piping
- Pressure sensor not reading
How to fix ch series e013 pump - full check: step by step
- Turn off power before unplugging connectors or measuring resistance.
- Press reset and see if the pump runs. Pressure should rise more than 3 psi when it runs.
- If stuck, turn the shaft with a flat screwdriver and retry.
- Check pump power at CN18. Power OK: check the capacitor and coil. No power = PCB.
- Bleed air from the piping.
- Pump runs but pressure does not change = pressure sensor, then PCB.
- If dirty water keeps sticking the pump, clean the heating piping before fitting a new pump.
If the unit shows an error code, look it up: Navien Combi Boiler codes
Models
CH-180 ASMECH-210 ASMECH-240 ASME
Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.13 13 Error p.84-85. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.