Navien Combi Boiler: CH series E010 air pressure (APS) – full check

Updated · by Aurora Star Tech Inc.

CH series E010 air pressure (APS) - full check on a Navien combi boiler: During pre-purge, E010 shows if the air pressure sensor never reaches ignition level after 5 tries (lockout). While firing, it shows if fan RPM runs 1,000 or more above target (shutdown, fan keeps running). It clears when RPM comes back within ±500.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series e010 air pressure (aps) - full check

  • APS hose torn, plugged or holding water
  • Venturi/burner hole plugged with soot
  • Condensate hose or trap blocked or frozen
  • Intake or exhaust blocked, dented, or holding rainwater
  • Exhaust being pulled back into the intake
  • Weak fan
  • Bad APS or PCB

How to fix ch series e010 air pressure (aps) - full check: step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check the APS hose for tears and water. Blow through it to check it is clear.
  3. Check the venturi hole for soot or debris.
  4. Check the condensate hose is not kinked or frozen. Pull the trap bottom and clear it.
  5. Check intake and exhaust pipes for dents, blockage and water (pipe sloping the wrong way).
  6. Check intake/exhaust spacing. Exhaust re-entering the intake causes noise and unstable APS/RPM.
  7. APS power: 4.5-5.5 VDC black to red at CN6. APS signal: 0.3-4.0 VDC black to white. Bad readings = replace APS.
  8. Very low fan RPM = replace the fan.
  9. If all checks pass, replace the APS, then the PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.11 10 Error p.78-80. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.