Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Navien Combi Boiler: CH series E009 fan motor RPM – full check

Updated · by Aurora Star Tech Inc.

CH series E009 fan motor RPM - full check on a Navien combi boiler: E009 shows when the fan RPM signal is 400 or less: during pre-purge (after 10 tries) or for 3 seconds while firing. The boiler locks out.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series e009 fan motor rpm - full check

  • No power to the fan from the PCB
  • Fan motor weak or failed
  • Wet fan connector
  • Loose white connector on the PCB

How to fix ch series e009 fan motor rpm - full check: step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Fan power: 120-180 VDC between black and red at CN8 (manual also gives 127-184 VDC). No power = PCB.
  3. Fan signal: 2-8 VDC between black and white at CN8 while running. Power OK but no signal or very low RPM = replace the fan.
  4. Check the fan plug for water. Fix the leak and dry it.
  5. Check the white connector on the PCB is seated.
  6. When refitting a fan, do not overtighten the screws with a drill (cracks the housing).
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.10 09 Error p.75-77; 8.2.4 p.122. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.