Navien Combi Boiler: CH series E004 false flame – full check

Updated · by Aurora Star Tech Inc.

CH series E004 false flame - full check on a Navien combi boiler: E004 means flame was seen when there should be none: before lighting (standby, pre-purge) or after the gas shut off (post-purge). The fan keeps purging. Auto reset.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series e004 false flame - full check

  • Main gas valve leaking through
  • Supply gas pressure too high pushing the valve open
  • Spark jumping from electrode to flame rod
  • Bad PCB

How to fix ch series e004 false flame - full check: step by step

  1. Gas work: licensed gas tech only. Turn off gas and power before opening the gas train, and leak-test every joint you opened.
  2. Look through the window. Flame before or after the burn = replace the main gas valve. If gas is leaking, shut the gas off and do not run the unit until repaired.
  3. Check inlet pressure: NG 6-10.5 in. W.C. If it is too high, fix the supply (regulator) and replace the main gas valve.
  4. Check flame rod position. Spark should not jump to the flame rod. Reposition or replace.
  5. Check CN19: 10-20 VDC, 7-20 µA. Flame signal with burner off = PCB.
  6. If all checks pass, replace the PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.5 04 Error p.69-70. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.