Updated · by Aurora Star Tech Inc.

CH series E001 boiling in heat exchanger - full check on a Navien combi boiler: E001 locks the boiler out when heating water stays at 208°F (98°C) or more for 15 seconds. The pump and fan keep running for post-purge until water drops to 167°F (75°C). Manual reset.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series e001 boiling in heat exchanger - full check

  • Circulation pump not running or weak
  • 3-way valve stuck
  • Heating strainer plugged
  • Main or DHW heat exchanger plugged
  • Heating supply/return or zone valves all closed
  • Supply thermistor reading wrong
  • Wrong capacity DIP setting on PCB
  • Bad PCB

How to fix ch series e001 boiling in heat exchanger - full check: step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Check the pump has 120 VAC while calling. No power at the pump = PCB.
  3. Touch the heating outlet pipe while heating. If it does not warm up, check the 3-way valve: Red+Black 120 VAC = heating, Blue+Black 120 VAC = hot water. Power there but no switch = valve. No power = PCB.
  4. Pull and clean the heating strainer. If it is full of debris, find where it comes from (e.g. corroded distributor).
  5. Make sure the heating supply/return valves are open and at least one zone/distributor valve is always open.
  6. Disconnect the heat exchanger pipes and blow through to check for blockage. If E001 only shows during hot water use, check the DHW heat exchanger.
  7. Compare the displayed supply temp with the real pipe temp. Unplug the thermistor and check 0.8-20 kOhm at CN13. Swap in a known-good sensor if unsure.
  8. Check the PCB DIP switch model/capacity setting.
  9. If all checks pass, replace the PCB.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.3 01 Error p.56-58. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.