Updated · by Aurora Star Tech Inc.

CH series breaker trips or remote has no power on a Navien combi boiler: Symptom guide for CH boilers that trip the breaker at plug-in or while running, or where the room controller is dead.

Homeowner with a combi boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Navien CH-180, CH-210, CH-240 and CH-240 ASME combi boilers

Common causes of ch series breaker trips or remote has no power

  • Damaged power cord or short
  • Transformer or PCB shorted
  • Wire pinched after a repair
  • Component shorting at a certain stage (e.g. stage 3 gas valve)
  • No DC power to the remote terminal

How to fix ch series breaker trips or remote has no power: step by step

  1. Turn off power before unplugging connectors or measuring resistance.
  2. Trips at plug-in: check the cord for damage. Then check the power transformer and the PCB.
  3. Trips after a repair: check every wire you moved. Watch the ignition transformer direction and do not pinch wires under the main gas valve.
  4. Trips while running: note when it happens. Example: trips when stage 3 opens = replace the gas manifold valve.
  5. Remote dead: check 19 VDC or more at the remote terminal. Low = check PCB output and wiring. OK = replace the remote.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Combi Boiler codes

Models

CH-180 ASMECH-210 ASMECH-240 ASME

Source: Navien CH Series Service Manual (CH-180/210/240/240 ASME, 1st ed. July 2010, No. 20A-GT-002), 5.28.2 p.111. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.