Updated · by Aurora Star Tech Inc.

TXV coil: low suction pressure, high superheat on a Navien air handler: What causes low suction with high superheat on a TXV coil.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

Common causes of txv coil: low suction pressure, high superheat

  • TXV too small
  • TXV superheat set too high
  • Restriction inside the indoor coil
  • Sensing bulb on the bottom of the suction line
  • External equalizer tube restricted or capped
  • Equalizer in the wrong spot (must be on the suction manifold after the last feeder tube)
  • Low charge
  • Plugged liquid line drier
  • Plugged TXV inlet strainer
  • Low outdoor temperature

How to fix txv coil: low suction pressure, high superheat: step by step

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Check the charge first.
  3. Check the bulb position and the equalizer tube.
  4. Check the drier and TXV strainer for a restriction.
  5. Then look at TXV size and setting.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Additional TXV Troubleshooting p.18-19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.