Navien Air Handler: TXV coil: high suction pressure, low superheat

Updated · by Aurora Star Tech Inc.

TXV coil: high suction pressure, low superheat on a Navien air handler: What causes high suction with low superheat (flooding) on a TXV coil.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

Common causes of txv coil: high suction pressure, low superheat

  • TXV too big
  • TXV seat leaking
  • TXV superheat set too low
  • Bulb not making good contact (loose clamp), not insulated, or in a warm spot
  • Weak compressor
  • Equalizer in the wrong spot (must be on the suction manifold after the last feeder tube)

How to fix txv coil: high suction pressure, low superheat: step by step

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Check the bulb clamp, insulation and location first.
  3. Check the equalizer line location.
  4. Check the compressor's pumping capacity.
  5. Then look at TXV size, setting and seat leakage.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Additional TXV Troubleshooting p.19. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.