Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Navien Air Handler: Leak sensor: verification test

Updated · by Aurora Star Tech Inc.

Leak sensor: verification test on a Navien air handler: How to test the leak mitigation system on a NAM coil.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NAM24B, NAM36B, NAM36C, NAM48C, NAM59C, NAM59D cased coils with TXV and refrigerant leak sensor

How to fix leak sensor: verification test: step by step

  1. Refrigerant work only by a certified tech. R-454B is mildly flammable: no open flame or sparks near a leak.
  2. Take off the coil access panel. The black sensor is near the bottom front of the coil.
  3. Cooling test: thermostat to COOL, fan AUTO, set below room temp. Confirm the compressor runs.
  4. Within 30 seconds of compressor start, let a small amount of refrigerant out at the sensor.
  5. Outdoor compressor and fan should stop, the indoor blower should keep running, and the ALARM wire should have no 24 V.
  6. About 5 minutes after the gas stops, the outdoor unit should come back on.
  7. Off-cycle test: thermostat OFF, wait for everything to stop, release a little gas at the sensor. The blower should start and ALARM should lose 24 V. The blower should stop about 5 minutes after the gas stops.
  8. If it does not work this way, check for loose or wrong wiring. Wiring good: replace the sensor.
  9. Put the panel back and set the thermostat back.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Source: Navien NAM Series cased coil (24-60K, R454B) Installation and Operation Manual, Verifying proper functioning of refrigerant leak mitigation system p.22-23. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Air Handler Emergency

647-657-2977