Navien Air Handler: Electric heat strip not heating

Updated · by Aurora Star Tech Inc.

Electric heat strip not heating on a Navien air handler: Blower runs but the electric heat does not warm the air.

Homeowner with a air handler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NASV/NASS 24B, 36C, 48D, 59D

Common causes of electric heat strip not heating

  • Open heating element
  • Open limit control
  • Failed heater contactor

How to fix electric heat strip not heating: step by step

  1. Check 208-240 VAC across contactor load terminals T1 and T2.
  2. Voltage present: power off and ohm the element. Open (infinite) = replace the element.
  3. No voltage on T1/T2 but voltage on L1/L2: check for an open limit and replace it.
  4. No voltage on T1/T2, voltage on L1/L2 and 24 VAC on the contactor coil: replace the contactor.
  5. 5 kW = 1 element, 10 kW = 2, 15 kW = 3 (two top, one bottom), 20 kW = two assemblies. Models up to 10 kW have one contactor, 15 and 20 kW have two.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.25-26. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.