Navien Air Handler: Electric heat model: ECM blower motor not running
Electric heat model: ECM blower motor not running on a Navien air handler: ECM motor checks with line voltage present.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
Common causes of electric heat model: ecm blower motor not running
- Line or low voltage wiring to the motor
- No call signal from the thermostat
- ECM control board fault
- Failed motor or motor module
How to fix electric heat model: ecm blower motor not running: step by step
- Confirm 208-230 VAC on the load side of the control box breaker.
- Check the line and low voltage wiring to the motor terminal block.
- With a call: 24 VAC between G and C on the ECM board (cooling or fan), or W1 and C (heat).
- Board check in heat: 24 VAC between connector pins 1 and 2. In cooling: pins 1 and 6, and pins 1 and 15. A meter will not read pins 4, 5, 7, 11.
- Board puts out the right signals: replace the motor or motor control module.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 7 Troubleshooting, p.23-24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.