Navien Air Handler: Blower runs nonstop and outdoor unit will not start (leak mitigation)
Blower runs nonstop and outdoor unit will not start (leak mitigation) on a Navien air handler: The refrigerant sensor has put the air handler in leak mitigation: blower on, 24 V to the outdoor contactor opened. The ALARM (orange) pigtail drops from 24 VAC to 0 VAC.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
Common causes of blower runs nonstop and outdoor unit will not start (leak mitigation)
- Real R-454B leak at the indoor coil
- Refrigerant sensor failed or at end of life (stays in mitigation)
How to fix blower runs nonstop and outdoor unit will not start (leak mitigation): step by step
- Ventilate the area. No open flames or sparks.
- Check for a leak with an A2L-rated portable leak detector.
- Leak found: repair it. The blower keeps running 5 minutes after the level at the sensor drops below its setpoint.
- No leak found but it stays in mitigation: replace the sensor with the approved Navien part, same location.
- ALARM wire: 24 VAC = normal, 0 VAC = leak detected.
Source: Navien NAS Series Air Handler Service Manual (24-60K, R-454B), 8 Refrigerant Leak Detection System, p.28-29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.