Navien Air Handler: Air handler or outdoor unit locks out, or transformer burns out (separate transformers)
Air handler or outdoor unit locks out, or transformer burns out (separate transformers) on a Navien air handler: When the air handler and the outdoor unit each have their own 24 V transformer, tying both to one R terminal (or leaving the RC-RH jumper in) connects two Class 2 circuits together.
Applies to: NASV/NASS 24B, 36C, 48D, 59D
Common causes of air handler or outdoor unit locks out, or transformer burns out (separate transformers)
- Both transformers wired to a single R terminal on the thermostat
- Jumper between RC and RH left in place
- Thermostat has no separate RC and RH terminals
How to fix air handler or outdoor unit locks out, or transformer burns out (separate transformers): step by step
- Power off before rewiring.
- Outdoor unit R (red) goes to RC on the thermostat. Air handler red pigtail goes to RH.
- Take out the RC-RH jumper if the thermostat has one.
- If the thermostat has only one R terminal, it has to be replaced with one that has RC and RH.
- Check both transformers; replace one that burnt out.
- Run the air handler and the outdoor unit one at a time to confirm each works.
Source: Navien NAS Series Air Handler Installation and Operation Manual (24-60K, R-454B), 9 Thermostat Wiring and Connections, p.29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.