Napoleon Gas Fireplace: Wall switch OFF but main burner comes on when gas knob turned ON
Wall switch OFF but main burner comes on when gas knob turned ON on a Napoleon gas fireplace: Wall switch off, gas knob to ON, main burner lights anyway. Napoleon GD70 STARfire direct vent. The switch is not breaking the circuit, so something is feeding the valve. Short or reversed switch most of the time.
Applies to: Napoleon GD70 STARfire direct-vent fireplace (GD70NT-S natural gas, GD70PT-S propane)
Common causes of wall switch off but main burner comes on when gas knob turned on
- Wall switch mounted upside down
- Wall switch shorted to ground
- Wall switch wire shorted to ground
- Faulty gas valve
How to fix wall switch off but main burner comes on when gas knob turned on: step by step
- Look at the switch orientation. Upside down, flip it around.
- Check the switch for a ground or short with a meter, power off. Replace the switch if shorted.
- Check the switch wire for a short to ground. Repair it or replace the wire.
- Switch and wire good, valve is the culprit. Replace the gas valve, and have a licensed gas tech do it.
- Leak test the new connections and confirm the burner shuts off with the switch before you leave
If the unit shows an error code, look it up: Napoleon Gas Fireplace codes
Models
Source: Napoleon GD70NT-S / GD70PT-S Installation & Operating Instructions W415-0434, Troubleshooting table, p.26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.