Napoleon Gas Fireplace: Test: thermocouple and thermopile millivolts
Test: thermocouple and thermopile millivolts on a Napoleon gas fireplace: Millivolt test for the generator on a Napoleon gas fireplace. Thermocouple or thermopile. Weak reading means weak pilot or a tired generator. Test, do not guess.
Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)
Common causes of test: thermocouple and thermopile millivolts
- Weak thermocouple or thermopile
- Poor pilot flame not heating the generator properly
How to fix test: thermocouple and thermopile millivolts: step by step
- Thermocouple (Robertshaw with adapter, or SIT 820 Nova at the solder button): open circuit should read 20-30 mV, closed circuit 10-15 mV.
- Thermopile open circuit: disconnect the leads from terminals 1 and 2, put the meter on mV across the thermopile leads. It should read 500 mV.
- Thermopile closed circuit: meter on terminals 1 and 2 with the main burner on. Minimum 150 mV.
- Low readings: check the pilot flame first. Clean the pilot and make sure the flame wraps the generator tip.
- Pilot good and still low, replace the generator
If the unit shows an error code, look it up: Napoleon Gas Fireplace codes
Models
Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 5 Testing & Adjustments, Testing: Millivolts, p.33-35. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.