Updated · by Aurora Star Tech Inc.

Test: gas inlet and manifold pressure on a Napoleon gas fireplace: This is a procedure for checking gas inlet and manifold pressure on Napoleon millivolt valves. You use it when the burner flame is low, the pilot starves, or you suspect the supply or regulator is out of spec. Inlet pressure tells you what the house is delivering, and manifold pressure tells you what the valve regulator is passing to the burner. Compare both to the figures below.

Homeowner with a gas fireplace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Napoleon gas fireplaces - direct vent, natural vent and vent-free (general service manual)

Common causes of test: gas inlet and manifold pressure

  • Burner flame low or lifting and you need to know if supply or valve regulator is at fault
  • Pilot dropping out when the burner lights, suggesting supply starvation
  • After a conversion or valve replacement, to confirm settings
  • Supply or regulator out of spec

How to fix test: gas inlet and manifold pressure: step by step

  1. Turn the inlet or outlet test screw 2-3 turns counter-clockwise and slip the gauge tube over the fitting
  2. Check inlet pressure with the main burner ON to confirm adequate flow, a reading that falls when the burner lights means supply trouble
  3. Spec (service manual): natural gas supply 7" w.c., manifold 3.5" w.c.; propane supply 11" w.c., manifold 10" w.c. (GD70 manual lists propane inlet 13" normal / 11" minimum)
  4. If inlet is good and manifold is off, the valve regulator is suspect, if inlet is low look upstream at the piping or the regulator
  5. Reseal screws firmly clockwise afterwards, do not over-torque; use a .150" x .030" blade screwdriver
  6. WARNING: leak-test the test ports with approved leak solution before leaving, and leave gas adjustments to a licensed technician
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Napoleon Gas Fireplace codes

Models

GD70NT-SGD70PT-S

Source: Napoleon (Wolf Steel) Service Manual W415-0118, Part 5 Testing & Adjustments, Testing: Pressures, p.31. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.