Icon
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Midea Furnace: No light and no fan – furnace does not start

Updated · by Aurora Star Tech Inc.

No light and no fan - furnace does not start on a Midea furnace: Furnace shows no LED activity and the blower does not run on a call for heat or fan.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A)

Common causes of no light and no fan - furnace does not start

  • No 115 V power to the furnace
  • Blower door switch open or door not closed
  • Blown fuse
  • Failed transformer
  • Thermostat not sending a call
  • Loose/wrong wiring
  • Blower motor or fan drive board failure
  • Control board failure

How to fix no light and no fan - furnace does not start: step by step

  1. WARNING: Discharge static before touching the control board; disconnect power before handling wiring.
  2. Check for 115 VAC between L1 and common at the furnace; if missing, check the supply at the connection box/disconnect.
  3. Make sure the blower access door is closed properly; with power off, press in the door switch and confirm 0 ohms. Replace the door switch if open.
  4. Check the board fuse; replace if blown. If the fuse is good, check the transformer secondary for 18-31 VAC and replace the transformer if it is dead.
  5. Check for 18-31 VAC between R and C; then check W/W1 to C (heating call) and G to C (fan call). No call = check thermostat settings or replace the thermostat.
  6. Check for loose wires or wrong connections and correct per the wiring diagram; leave the PARK terminal unused.
  7. If the board receives the call but nothing happens, check for 18-31 VAC between the speed tap (hi-heat/lo-heat/hi-cool/lo-cool) and COM and 115 VAC between CIRC-H and N. Replace the board if outputs are missing.
  8. If the motor gets signal and power but does not turn, measure resistance between motor leads U, V and W (should be 2-10 ohms). If in range, replace the fan drive board; if not, replace the motor.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Midea Furnace codes

Models

BGH96M060B3ABGH96M080B3ABGH96M080C4ABGH96M100C5ABGH96M100D5ABGH96M120D5A

Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Section 3.1 chart and Figs. 1-8, p.7-9. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Furnace Repair

647-657-2977