Lifebreath Hrv: Dehumidistat does not work
Dehumidistat does not work on a Lifebreath hrv: The HRV does not go to high speed when the house is humid.
Applies to: BC02, BC03, DXPL02 controls with dehumidistat
Common causes of dehumidistat does not work
- Outdoor temperature above 15°C (59°F) for 24 h, so the auto disable shut the dehumidistat off
- Dehumidistat set to OFF
How to fix dehumidistat does not work: step by step
- Check the outdoor temperature. Above 15°C (59°F) for a full day the control turns the dehumidistat off by itself. That is normal.
- It turns back on after 24 h below 15°C (59°F), or after the HRV is unplugged for 30 seconds.
- Check the setting on the control and set it to the level wanted.
If the unit shows an error code, look it up: Lifebreath Hrv codes
Models
Source: Lifebreath RNC5-ES Homeowner's Guide (69-RNC5-OWNERS 012616), How the Dehumidistat Works, p. 4; Troubleshooting, p. 14. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.