Lennox General: Smart Room Sensor not included in temperature averaging
Smart Room Sensor not included in temperature averaging on a Lennox general: Sensor is left out of the averaged room temperature.
Applies to: Lennox Smart Room Sensor, not compatible with iHarmony zoning
Common causes of smart room sensor not included in temperature averaging
- Sensor reading differs from thermostat by more than 7°F
- Occupancy detection is ON and the room is not occupied
- Sensor is in direct sunlight, near discharge air, or in unconditioned space
How to fix smart room sensor not included in temperature averaging: step by step
- Open the sensor detail screen and read the warning message.
- Move the sensor away from sunlight, vents or unconditioned space if needed.
- Confirm the occupancy setting matches how the room is used.
- Replace the sensor if the location is suitable and readings are still wrong.
If the unit shows an error code, look it up: Lennox General codes
Source: Lennox S40 Smart Thermostat User Guide, p. 38-39. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.