Lennox Furnace: Ignitor glows but burners do not light

Updated · by Aurora Star Tech Inc.

Ignitor glows but burners do not light on a Lennox furnace: Inducer runs, the ignitor heats up and glows, and then no flame. What I usually find is gas pressure that is out of range, a loose plug on the gas valve, or a valve that never got its 24 volts. Start by working out whether gas is reaching the burners and whether the valve is being told to open. Gas work is for a qualified gas technician, so if you are not one, stop at the voltage checks.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: G43UF-24B-045 through G43UF-60D-135 (SureLight boards 32M88, 78M47, 100973-01)

Common causes of ignitor glows but burners do not light

  • No gas or line pressure out of range
  • Gas valve or plug wiring miswired or loose
  • Gas valve failed
  • Control not supplying 24 V

How to fix ignitor glows but burners do not light: step by step

  1. Gas work: qualified gas tech only
  2. Check line pressure at the valve. It should stay at or below 13 in. WC. Minimum is 4.5 in. WC natural gas and 8.0 in. WC propane
  3. Check the gas valve wiring and the multi-pin plugs for loose connections
  4. About 35 seconds after the heat call, check for 24 V at the valve
  5. Replace the valve if 24 V is present and it does not open
  6. Replace the control if there is no 24 V
  7. Confirm the manual shutoff is open and the tank has fuel if on propane
  8. Check for gas leaks with approved detector after any work
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Lennox Furnace codes

Models

G43UF-24B-045G43UF-24B-070G43UF-36B-070G43UF-36C-090G43UF-36C-090HG43UF-48C-090G43UF-48C-110G43UF-48C-110HG43UF-60C-110G43UF-60D-135

Source: Lennox G43UF Unit Information Corp. 0416-L4, Troubleshooting Chart Problem 4 p.53. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.