KeepRite Heat Pump: Outdoor unit will not run or will not defrost – KeepRite heat pump defrost board (FAST 1173636/1177927/1190281)

Updated · by Aurora Star Tech Inc.

Outdoor unit will not run or will not defrost - KeepRite heat pump defrost board (FAST 1173636/1177927/1190281) on a KeepRite heat pump: Checks on the time/temperature defrost board used in these heat pumps.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: KeepRite split heat pumps using FAST 1173636, 1177927 or 1190281 defrost boards

Common causes of outdoor unit will not run or will not defrost - keeprite heat pump defrost board (fast 1173636/1177927/1190281)

  • No 24 V on Y from the thermostat
  • Open pressure switch
  • Bad contactor
  • No 24 V on T1
  • Defrost thermostat stuck
  • Bad pigtail harness

How to fix outdoor unit will not run or will not defrost - keeprite heat pump defrost board (fast 1173636/1177927/1190281): step by step

  1. Unit will not run: check 24 V at the Y input, then at the Y spade (goes out through the pressure switches to the contactor).
  2. Y spade has 24 V but the contactor is open: check coil voltage; none means an open pressure switch, voltage present means a bad contactor.
  3. Contactor closed but nothing runs: check wiring, capacitor and compressor.
  4. No defrost: jumper DFT to R, short the speed-up pins (timer runs 256x faster; 90 min setting takes about 21 s).
  5. Still no defrost: confirm 24 V on T1 (fed once Y is on and switches are closed).
  6. During forced defrost, expect 24 V between C and W2; afterwards remove the DFT jumper or the unit will defrost every interval for the full 10 minutes.
  7. A stuck-closed defrost thermostat gives a 10-minute defrost every interval; stuck open means no defrost.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: KeepRite Heat Pump codes

Models

KeepRite *CA/*CH Two-Stage Communicating

*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960

KeepRite *SA/*SH Single-Stage Communicating

*SH4*SH5*SH6

KeepRite N4H4/R4H4/WCH4/NXH5 Heat Pump

N4H4NXH5R4H4R4H449WCH4

Source: KeepRite_ICP_KeepRite_Tempstar_Heil_split_A_C_HP_R_410A_R_22_service_421_08_5400_04.txt - section Defrost Control Boards / Troubleshooting (FAST 1173636/1177927/1190281). Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.