KeepRite Heat Pump: Forcing a defrost to test the board – KeepRite N4H4/R4H4/WCH4/NXH5
Forcing a defrost to test the board - KeepRite N4H4/R4H4/WCH4/NXH5 on a KeepRite heat pump: Steps to force a defrost cycle and confirm the defrost board, thermostat and reversing valve work.
Applies to: KeepRite N4H4, R4H4, WCH4, NXH5 heat pumps
Common causes of forcing a defrost to test the board - keeprite n4h4/r4h4/wch4/nxh5
- Defrost thermostat stuck open or closed
- Defrost board fault
- Reversing valve not shifting
How to fix forcing a defrost to test the board - keeprite n4h4/r4h4/wch4/nxh5: step by step
- Quiet Shift-2 boards: short the J1 speed-up pins for 5 s and release. With the defrost thermostat open you only get a short test defrost; with it closed a full defrost starts.
- Other boards: power off, unplug the outdoor fan lead (OF2 on PSC units, ODF on ECM units) and tape it.
- Run in heat until the liquid line drops below about 30°F so the defrost thermostat closes.
- Short the speed-up terminals; release the moment the reversing valve shifts, or the 10-minute defrost is skipped in about 2 s.
- Defrost should end when the coil/liquid line reaches about 65°F or when time runs out.
- Power off and reconnect the fan lead when done.
If the unit shows an error code, look it up: KeepRite Heat Pump codes
Models
KeepRite *CA/*CH Two-Stage Communicating
*CH624*CH636*CH648*CH660*CH924*CH936*CH948*CH960
KeepRite *SA/*SH Single-Stage Communicating
KeepRite N4H4/R4H4/WCH4/NXH5 Heat Pump
Source: KeepRite/ICP N4H4/R4H4/WCH4/NXH5 Installation Instructions 428 01 5107 10, Defrost / Defrost Speedup p.7-8. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.