KeepRite Furnace: Run the furnace component self-test (9MXE / 9MXT)
Run the furnace component self-test (9MXE / 9MXT) on a KeepRite furnace: Runs inducer, igniter and blower speeds briefly; gas valve and humidifier terminal are not energized. Will not start with a thermostat signal or running delays. Holding the jumper longer than 2 seconds makes the LED flash code 10 and the request is ignored.
Applies to: (F/G)9MXE and (F/G)9MXT furnaces
How to fix run the furnace component self-test (9mxe / 9mxt): step by step
- Remove the blower door, disconnect the thermostat R lead at the control and hold the blower door switch closed
- Jumper terminal C to the TEST/TWIN quick-connect for about 2 seconds, until the LED goes off, then remove the jumper
- The LED repeats the previous status code 4 times, then the inducer starts
- 9MXT: igniter on after 7 s for 15 s; blower LO-HT, HI-HT, COOL speed 10 s each; inducer low for 10 s and stops
- 9MXE: igniter on after 7 s for 15 s; blower continuous-fan, heat and cool speed 10 s each; inducer stops
- Reconnect R, restore the door, confirm the furnace shuts down and restarts from the thermostat
If the unit shows an error code, look it up: KeepRite Furnace codes
Models
KeepRite (F/G)9MXE Single-Stage Furnace
G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422A
KeepRite (F/G)9MXT Two-Stage Furnace
G9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A
More service & test modes tips for furnace
Source: KeepRite ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Component Self-Test, p.14-15; (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, p.14-15. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.