KeepRite Furnace: Reading stored codes and component test – KeepRite (F/G)9MXT

Updated · by Aurora Star Tech Inc.

Reading stored codes and component test - KeepRite (F/G)9MXT on a KeepRite furnace: How to recall the last fault and run the built-in component test.

Homeowner with a furnace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: KeepRite (F/G)9MXT furnaces

Common causes of reading stored codes and component test - keeprite (f/g)9mxt

  • Need to find the last fault after it cleared

How to fix reading stored codes and component test - keeprite (f/g)9mxt: step by step

  1. Remove any thermostat call and wait for delays to finish - codes cannot be read otherwise.
  2. Leave 115 V on. Briefly (2-3 s) jumper TEST/TWIN to the thermostat C terminal (or briefly open one main limit wire).
  3. A stored code flashes 4 times, then the component test starts. No stored code = test starts straight away.
  4. During the test the inducer runs throughout; the igniter and each blower speed run 10-15 s in turn. Gas valve and HUM are not powered.
  5. Stored codes survive power loss and are cleared after 72 hours.
  6. Reading a code: count the short flashes for the first digit; the digit after + is the count of long flashes.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: KeepRite Furnace codes

Models

KeepRite (F/G)9MXE Single-Stage Furnace

G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422A

KeepRite (F/G)9MXT Two-Stage Furnace

G9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A

KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace

G96VTN0401410G96VTN0401712G96VTN0601412G96VTN0601714G96VTN0801716G96VTN0802120G96VTN1002120G96VTN1002122G96VTN1202422

Source: KeepRite/ICP (F/G)9MXT Service and Technical Support Manual 440 04 4321 10, Retrieving Stored Fault Codes / Component Self-Test p.14, Fig. 16 p.24. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.