KeepRite Furnace: No heat, control ignores the thermostat – KeepRite (F/G)9MXE
No heat, control ignores the thermostat - KeepRite (F/G)9MXE on a KeepRite furnace: KeepRite (F/G)9MXE. Green status light pulses heartbeat, so the board is alive. Furnace ignores W, Y or G. Control is fine on its own, so the call is not getting in. Find the 24 V.
Applies to: KeepRite (F/G)9MXE furnaces
Common causes of no heat, control ignores the thermostat - keeprite (f/g)9mxe
- Thermostat or thermostat cable fault
- Thermostat not compatible with the control
- Failed furnace control
How to fix no heat, control ignores the thermostat - keeprite (f/g)9mxe: step by step
- Confirm the green light is pulsing (heartbeat), if not, use the LED codes first
- With a call, measure 24 V at W, Y1, Y/Y2 or G on the board
- No 24 V: check the thermostat and cable for breaks and loose terminals
- 24 V present but no response: replace the control
- If calling for heat directly at the board with a test lead works but the thermostat does not, the thermostat is not compatible: add a ballast resistor, connect the C terminal, or change the thermostat
- Remove the test lead and restore wiring when done
- Power off before changing any wiring
If the unit shows an error code, look it up: KeepRite Furnace codes
Models
KeepRite (F/G)9MXE Single-Stage Furnace
G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422A
KeepRite (F/G)9MXT Two-Stage Furnace
G9MXT0401410AG9MXT0401712AG9MXT0601412AG9MXT0601714AG9MXT0801716AG9MXT0802120AG9MXT1002120AG9MXT1202422A
KeepRite (F/G)96VTN Two-Stage Variable-Speed Furnace
G96VTN0401410G96VTN0401712G96VTN0601412G96VTN0601714G96VTN0801716G96VTN0802120G96VTN1002120G96VTN1002122G96VTN1202422
Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Fig. 16 flow chart, p.24. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.