KeepRite Furnace: Cut the cooling blower off-delay to 5 seconds (9MXE)
Cut the cooling blower off-delay to 5 seconds (9MXE) on a KeepRite furnace: The cooling blower off-delay is 90 s; jumpering Y/Y2 or Y1 to DHUM cuts it to 5 s. The DHUM input logic is reversed: 24 V means no dehumidify call.
Applies to: KeepRite (F/G)9MXE
How to fix cut the cooling blower off-delay to 5 seconds (9mxe): step by step
- Jumper Y/Y2 or Y1 to the DHUM terminal on the control
- Cooling blower off-delay then drops from 90 s to 5 s
If the unit shows an error code, look it up: KeepRite Furnace codes
Models
G9MXE0401410AG9MXE0401714AG9MXE0601412AG9MXE0601714AG9MXE0801716AG9MXE0802120AG9MXE1002120AG9MXE1202422A
More settings shortcuts tips for furnace
Source: KeepRite/ICP (F/G)9MXE Service and Technical Support Manual 440 04 4311 09, Sequence of Operation p.26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.