ICP Heat Pump: Defrost not working – test the defrost board

Updated · by Aurora Star Tech Inc.

Defrost not working - test the defrost board on a ICP heat pump: Time/temperature defrost board: interval 30/60/90 min (factory 90). Defrost thermostat closes at 32F (0C) and opens at 65F (18C). Defrost limited to 10 minutes.

Homeowner with a heat pump problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: ICP N4H3 R-410A split heat pump (manual 428 01 5103 02); Comfort Alert codes apply only to units factory-fitted with the Comfort Alert module

Common causes of defrost not working - test the defrost board

  • Defrost thermostat open or loose on its tube stub
  • Wrong interval jumper
  • Failed defrost board

How to fix defrost not working - test the defrost board: step by step

  1. Confirm the defrost thermostat is tight on the tube stub at the coil end plate.
  2. Check the defrost thermostat: 24 V across DFT = open, 0 V = closed. Or jumper the DFT terminals to bypass it.
  3. If open, force frost: power off, disconnect fan lead at OF2 and tape it, run in heat until 0 V across DFT, then power off and reconnect OF2.
  4. Run in heat with DFT closed; short the SPEEDUP pins until the reversing valve shifts (normally 1-21 seconds).
  5. In defrost the reversing valve shifts, outdoor fan stops and strip heat comes on.
  6. Remove the short right away for a short defrost (ends at 65F or timer); holding it more than 2 seconds after the shift returns the unit to heating.
  7. Unit must return to heat: valve shifts back, fan restarts, strip heat off. If not, replace the board.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: ICP Heat Pump codes

Models

N4H3

Source: ICP N4H3 Installation Instructions 428 01 5103 02, Defrost System, p.13-14. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.