HTP Boiler: Lockout on ignition (F09, no flame)
Lockout on ignition (F09, no flame) on a HTP boiler: Boiler tries to light four times on one call and locks out.
Applies to: EL-80, EL-110, EL-150, EL-220, EL-299, EL-399 (N/LP)
Common causes of lockout on ignition (f09, no flame)
- Spark electrode gap wrong or corroded
- No gas / low gas pressure / air in line
- Dirty flame rectifier
- Blocked flue or condensate
How to fix lockout on ignition (f09, no flame): step by step
- Watch the igniter through the sight glass
- Set electrode gap to 0.196 in. (5 mm +/-1) and clean corrosion
- Measure gas inlet pressure; 3.5 to 14 in. w.c. with no more than 1 in. drop on light-off
- New or empty LP installs: make sure the line was purged
- Check the flame rectifier
- Check flue and condensate for blockage
If the unit shows an error code, look it up: HTP Boiler codes
Models
EL-80 LPEL-80 NEL-110 LPEL-110 NEL-150 LPEL-150 NEL-220 LPEL-220 NEL-299 LPEL-299 NEL-399 LPEL-399 N
Source: Elite EL-80 N Installation Manual (LP-293), p. 71, p. 38. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.