Heat & Glo Gas Fireplace: Fireplace with PVK-80 power vent: flames lifting or jumping

Updated · by Aurora Star Tech Inc.

Fireplace with PVK-80 power vent: flames lifting or jumping on a Heat & Glo gas fireplace: Flame tuning on a Heat-N-Glo DSI fireplace with the PVK-80 power vent; also covers the short delay before ignition.

Homeowner with a gas fireplace problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Heat-N-Glo DSI fireplaces with PVK-80 power vent (Fenwal, RAM-1-RS, RAM 1MC1 systems)

Common causes of fireplace with pvk-80 power vent: flames lifting or jumping

  • Exhaust control lever opened too far (tall, lifting, ghosting flames)
  • Exhaust control closed too far (short, active, jumping flames)
  • No 120 VAC at the fireplace junction box
  • Power vent plugged into the wrong receptacle (RAM-1-RS uses AUX, not REM)

How to fix fireplace with pvk-80 power vent: flames lifting or jumping: step by step

  1. CAUTION: Disconnect power to the fireplace before any work on the power vent.
  2. A short delay before ignition is normal: the fan has to reach speed and purge the firebox first.
  3. The power vent needs 120 VAC at the fireplace junction box. On RAM-1-RS units it plugs into AUX, not REM. Match wire colors on the terminal block.
  4. Start with the exhaust control lever closed. Short, active, jumping flames: open the lever slightly and recheck until flames are steady.
  5. Tall, lifting, floating or ghost-like flames: the lever is open too far; close it until that stops.
  6. When flames are right, lock the lever to the housing with the sheet-metal screw and leave the setting alone.
  7. PVK-80 is for DSI fireplaces only; standing-pilot (millivolt) units cannot use it, and no other appliance may share the vent.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Heat & Glo Gas Fireplace codes

Models

CFX-DAGrand-50-CRAM-1-RSRAM 1MC1-01RAM 1MC1-05

Source: Heat-N-Glo DSI / HSI Troubleshooting Guide (Professional Development), Section 8 Power Vent PVK-80, p.56-61. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.