Goodman Heat Pump: Outdoor coil iced / no defrost – R-32 GLZS/ALZS heat pump
Outdoor coil iced / no defrost - R-32 GLZS/ALZS heat pump on a Goodman heat pump: Outdoor coil builds ice in heating and the unit does not go into defrost, or defrost does not end properly.
Applies to: R-32 GLZS4/5 and ALZS4/5 heat pumps
Common causes of outdoor coil iced / no defrost - r-32 glzs/alzs heat pump
- Defrost thermostat not closing or mounted badly
- Defrost control board fault
- Reversing valve or outdoor fan relay problem
How to fix outdoor coil iced / no defrost - r-32 glzs/alzs heat pump: step by step
- With power on and the unit idle, jumper DFT to R (R-DFT) on the defrost board.
- Move the timer jumper to the TEST pins (use the proper jumper, not a screwdriver), call for heat - the unit should enter defrost within 21 seconds; then remove the test jumper at once.
- In defrost check: 24 V across C and O; line voltage (208-230 VAC) across DF1 and DF2 (fan relay open); 24 V across W/W2 and C.
- If any reading is wrong, replace the defrost board.
- Test the defrost thermostat with a thermocouple on the adjacent tube: closing and opening temperatures depend on the part (see Specs tab).
- Power off, remove the DFT jumper and put the timer jumper back on the chosen 30/60/90 minute pins before leaving.
If the unit shows an error code, look it up: Goodman Heat Pump codes
Models
Goodman/Amana R-32 GLZS/ALZS
ALZS4BA**10AAALZS4NA**10AAALZS5BA**10AAGLZS4BA**10AAGLZS4MA**10AAGLZS5BA**10AA
Goodman/Amana R-410A GSZ/ASZ/DSZ (ANZ/SSZ/VSZ)
ANZ130181ANZ130241ANZ130301ANZ130361ANZ130421ANZ130481ANZ130601ANZ140181ANZ140241ANZ140301ANZ140361ANZ140421ANZ140481ANZ140491ANZ140601ASZ130181ASZ130241ASZ130301ASZ130361ASZ130421ASZ130481ASZ130601ASZ140181ASZ140241ASZ140301ASZ140361ASZ140381ASZ140421ASZ140481ASZ140491ASZ140601ASZ160181ASZ160241ASZ160301ASZ160361ASZ160421ASZ160481ASZ160601ASZ180361ASZ180481ASZ180601ASZH5***10DSZ160241DSZ160361DSZ160481DSZ160601DSZ180361DSZ180481DSZ180601GSZ110903GSZ110904GSZ111203GSZ111204GSZ130181GSZ130191GSZ130241GSZ130251GSZ130301GSZ130311GSZ130361GSZ130363GSZ130371GSZ130421GSZ130481GSZ130483GSZ130484GSZ130601GSZ140181GSZ140241GSZ140301GSZ140361GSZ140371GSZ140421GSZ140481GSZ140491GSZ140601GSZ160181GSZ160241GSZ160301GSZ160361GSZ160421GSZ160481GSZ160601GSZH5***10SSZ140181SSZ140191SSZ140241SSZ140251SSZ140301SSZ140311SSZ140361SSZ140371SSZ140381SSZ140421SSZ140481SSZ140601SSZ160241SSZ160361SSZ160421SSZ160481SSZ160601VSZ130181VSZ130241VSZ130301VSZ130361VSZ130421VSZ130481VSZ130601VSZ140181VSZ140241VSZ140301VSZ140361VSZ140421VSZ140481VSZ140491VSZ140601
Goodman/Amana ComfortNet ASZC/GSZC/DSZC
ASZC160241ASZC160361ASZC160421ASZC160481ASZC160601ASZC180241ASZC180361ASZC180481ASZC180601DSZC160241DSZC160361DSZC160481DSZC160601DSZC180361DSZC180481DSZC180601GSZC160241GSZC160361GSZC160481GSZC160601GSZC180241GSZC180361GSZC180481GSZC180601
Source: Goodman RS6200301 R-32 GLXS/ALXS/GLZS/ALZS service (07-2024), Testing Defrost Control / Defrost Thermostat p.32-33. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.