Glow Brand Boiler: Removing an existing boiler from a common venting system
Removing an existing boiler from a common venting system on a Glow Brand boiler: Use this procedure for each boiler that stays on a common vent after another boiler is removed. The remaining venting is usually too large and must be resized.
Applies to: Remaining appliances on a common vent
How to fix removing an existing boiler from a common venting system: step by step
- Shut down all boilers on the common venting system before starting.
- Seal any unused openings in the common vent.
- Check the venting for correct size, horizontal pitch, blockage, restriction, leakage, corrosion and other faults.
- Close building doors and windows. Run clothes dryers, exhaust fans and other non-vented appliances. Set exhaust fans to maximum. Close fireplace dampers.
- Start the remaining appliance and run it continuously.
- Test for spillage at the draft hood relief opening after 5 minutes of main burner operation using a match, candle or smoke.
- If the appliance vents correctly, restore doors, windows, fans, dampers and other appliances to normal use.
- Correct any improper operation and resize the common vent to approach the minimum size in the National Fuel Gas Code tables (Chapter 13) or CAN/CSA B149.1.
If the unit shows an error code, look it up: Glow Brand Boiler codes
Source: Glow Brand C95 & C140 installation & operating manual, p. 18. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.