Glow Brand Boiler: Low water cut-off (LWCO) wiring and test
Low water cut-off (LWCO) wiring and test on a Glow Brand boiler: LWCO on the Glow C95/C140. Field wired, then tested. A jumper stays on 1 and 2 only when no switch is fitted. Don't leave a jumper in place of a switch you need. The test is what proves the burner drops out on low water.
Applies to: C95 & C140
Common causes of low water cut-off (lwco) wiring and test
- LWCO switch wired to the wrong terminals or wrong wire
- Factory jumper left across 1 and 2 when a switch is installed, defeating the cutoff
- LWCO that does not shut the burner down when the water level drops
How to fix low water cut-off (lwco) wiring and test: step by step
- Leave the factory jumper between terminals 1 and 2 only when no LWCO switch is fitted.
- Wire the LWCO switch into the terminal strip as shown in Figure 9.6, using up to 20 ft of 18 ga LVT.
- Test the LWCO by lowering the water level and confirm the burner shuts down (see Special Operations, section 11.9).
- Restore the water level and confirm the boiler restarts.
- Never run the boiler with the cutoff bypassed.
If the unit shows an error code, look it up: Glow Brand Boiler codes
Source: Glow Brand C95 & C140 installation & operation manual, p. 49. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.