Glow Brand Boiler: Condensate trap cleaning
Condensate trap cleaning on a Glow Brand boiler: Clean the condensate trap and confirm condensate flow after reassembly.
Applies to: C95 & C140 Glow Combi boilers
Common causes of condensate trap cleaning
- Sediment in the condensate trap or hose
- Restriction in the condensate drain line
How to fix condensate trap cleaning: step by step
- Close the manual gas shutoff valve and remove power to the unit.
- Remove the front door panel.
- Remove the flue gas inlet plug from the condensate trap. Do not pull hoses down away from their upper connections. Keep the silicone hose secured to the plug.
- Unthread the retaining nut and disconnect the corrugated condensate hose from the trap outlet.
- Unthread the inlet cap from the trap.
- Remove the trap from the unit.
- Clean the trap and hose with water. Check the lower connection port for sediment. The float can be removed for cleaning if needed.
- Reinstall the trap, connect the hose to the trap outlet, and thread the inlet cap and retaining nut.
- Fill the trap three-quarters full with water through the flue gas inlet. Check all connections for leaks. Refit the flue gas inlet plug.
- Reinstall the front door panel.
If the unit shows an error code, look it up: Glow Brand Boiler codes
Source: C-300 C95-C140 Installation & Operation Manual, p. 76. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.