Glow Brand Boiler: Condensate drain installation
Condensate drain installation on a Glow Brand boiler: Route condensate to a drain properly so the boiler does not shut down or the trap does not fail.
Applies to: Condensate drain and trap
Common causes of condensate drain installation
- Frozen or blocked drain line causes condensate to back up into the combustion chamber.
- Corrosive condensate attacks metal drains and sewer pipes.
How to fix condensate drain installation: step by step
- Do not run condensate lines outdoors.
- Do not use copper, steel or galvanized pipe for the condensate disposal system.
- Use the supplied 3/4 in I.D. corrugated hose to connect the trap to the drain. Extend it with poly or vinyl tubing if needed.
- Check local rules on whether condensate must be neutralized before disposal.
- If a condensate pump is needed, select one designed for condensate.
- Do not replace the factory condensate trap with another trap.
- Keep the trap secure to the bottom of the boiler with no strain on it.
- Keep the drain line away from areas that leaking condensate could damage.
If the unit shows an error code, look it up: Glow Brand Boiler codes
Source: Glow Brand C95 & C140 installation & operating manual, p. 31. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.