Glow Brand Boiler: Boiler shows FILL and will not fire
Boiler shows FILL and will not fire on a Glow Brand boiler: Display shows FILL, burner will not fire. Low water pressure is the lock.
Applies to: C95 & C140
Common causes of boiler shows fill and will not fire
- Water pressure below 4 PSI at the boiler inlet
- Water pressure below 10 PSI, which the pressure sensor uses to inhibit firing
- Slow leak, failed expansion tank or fill valve that is not holding pressure
How to fix boiler shows fill and will not fire: step by step
- Read the pressure on the boiler gauge or display, with the system cold.
- Refill the system to at least 10 PSI.
- Find and repair leaks, because pressure that keeps dropping means water is going somewhere.
- Check the expansion tank charge and the fill valve.
- Confirm the burner fires after pressure is restored.
If the unit shows an error code, look it up: Glow Brand Boiler codes
Source: Glow Brand C95 & C140 installation & operation manual, pp. 33-34. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.